3-7
Planning Before Installing
GV3000/SE
HP Rating
Filter Type
Maximum Lead Length in Feet with
230 VAC Motor
Carrier Frequency
30
40
50
60
75
100
30
40
50
60
75
100
None
A 5%MTE
reactor/filter
at the drive.
2 kHZ
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
4 kHZ
500
500
500
500
500
500
1000
1000
1000
1000
1000
1000
8 kHZ
500
500
500
500
500
500
1000
1000
1000
1000
1000
1000
Table 3.6 - Motor Lead Lengths
Table 3.7 - Reactors
Note that the lead lengths listed are valid with Reliance Electric inverter duty motors.
GV3000/SE
HP Rating
30
40
50
240 Volt
5% MTE Reactor
RL-08002
RL-10002
RL-13002
GV3000/SE
HP Rating
60
75
100
240 Volt
5% Reactor
RL-16002
RL-20002
RL-25002
GV3000/SE
Drive
GV3000/SE
Drive
GV3000/SE
Drive
GV3000/SE
Drive
Motor
Motor
Motor
Motor
Motor
Motor
Motor
38 m (125')
38 m (125')
15 m (50')
61 m (200')
8 m (25')
61 m (200')
8 m (25')
76 m (250')
All examples represent 76 m (250') of motor lead length.
Figure 3.3 - How to Measure Motor Lead Lengths
These part numbers are for a reactor with a cacitor filter.
MTE standard reactors can be used on GV3000/SE drives with carrier frequency settings up to 8 kHZ.
All reactors are UL-recognized (UL-506 File #E53094) and CSA certified (CSA File #LR29753).