Wiring the Regulator Board Terminal Strip
Parameters/Wiring Connections
The following parameters must be set:
P.026: Function Loss Response
A signal must be present at terminal 20 for the drive to be able to
start. See figures 7.1 and 7.2 The drive is shipped from the factory
with a jumper between terminals 16 and 20 which provides the
signal. The function loss input should be in series with the drive's
external interlocks. In this case, the jumper must be removed
before the connections are made. See figure 2.7.
Terminal 20 On = No Function Loss
The following parameters must be set:
P.000: Control Source
P.020: Jog Speed Reference
P.021: Jog Ramp Accel Time
P.022: Jog Ramp Decel Time
Terminal 21 On = Jog Operation
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
20
21
Description
Digital Input 5
(Function Loss)
Digital Input 4
(Run/Jog)
Wiring a Function Loss Input
16 17 18 19 20 21
16 17 18 19 20 21
REMOVE FACTORY FUNCTION
LOSS JUMPER HERE.
FUNCTION LOSS
COAST-STOP
PUSH-BUTTON
SAFETY INTERLOCKS
TERMINAL STRIP
16
21
RUN
JOG
Wiring a Run/Jog Input