PowerFlex® 700S and 700H Fan Inverter Upgrade Kit (Frame 10-11)

What You Need to Do

❐ Step 1: Remove power from the drive.

❐ Step 2: Remove the covers from the power structure.

❐ Step 3: Prepare the power structure for inverter assembly removal.

❐ Step 4: Remove the old inverter assemblies from the drive.

❐ Step 5: Remove the inverters from the old assemblies.

❐ Step 6: Install the inverters on the new assemblies.

❐ Step 7: Install the new inverter assemblies and prepare the drive for

use.

Step 1: Removing Power
from the Drive

1. Turn off and lock out input power. Wait five minutes.

2. Verify that there is no voltage at the drive’s input power terminals.

3. Measure the DC bus voltage at the DC+ & DC- terminals on the Power

Terminal Block. The voltage must be zero.

!

ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before performing
any work on the drive. Measure the DC bus voltage at the DC+ &
DC- terminals of the Power Terminal Block. The voltage must be
zero.

Remove power before making or breaking cable connections.
When you remove or insert a cable connector with power
applied, an electrical arc may occur. An electrical arc can cause
personal injury or property damage by:

• sending an erroneous signal to your system’s field devices,

causing unintended machine motion

• causing an explosion in a hazardous environment

Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.