2-2
Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:
Troubleshooting and Maintenance Manual (AADvance
Controller)
Preventive Maintenance Schedule
Table 1:
Recommended Schedule for Preventive Maintenance
Preventive Maintenance Task
Interval
Review status LEDs
Daily
Check fuses
3 months
Check wiring terminals
3 months
Check seating of plug-in components
3 months
Check for contamination, general condition and
adequate environmental protection
3 months
Check ground connection
3 months
Check analogue input module calibration
2 years
Check digital input module calibration
3 years
Check analogue output module calibration
2 years
Perform manual test
Manual Test Interval
Note: Testing of the logic solver and its associated field devices must be carried out according to the
appropriate plant or process safety analysis and the safety integrity validation. The manual test interval
is used by the Probability of Failure on Demand (PFD) data analysis as part of the certification process.
Refer to the document "PFH and PFD Data for AADvance Controllers" - Doc No: 553847.
Check Fuses
To check the controller fuses do the following: