Fault Reporting Reference Information
Each module has a set of front panel status indicators. The purpose and meaning of these indicators
relevant to each module is as follows:
Status Indicators on the T9110 Processor Module
Table 2:
Status Indicators on the 9110 Processor Module
Indicator
Status
Description
Healthy
Provides an indication of the module's fault status and power-
on/operational status
OFF
No power
RED
Module has a fault
Flashes RED briefly after being installed as the
module is booting up or reset is in progress
controller is off-line
GREEN
As the module is installed and receives power it flashes RED for a second
then goes GREEN as the module boots up (10 to 20 seconds).
When the module has booted up and is operational the LED stays GREEN
and indicates that the module has no hardware faults.
When in the recovery Mode and no faults are present the LED is GREEN
Note: