3-6

Document: 553634

(ICSTT-RM406F_EN_P) Issue: 089:

Troubleshooting and Maintenance Manual (AADvance
Controller)

A module fault (below)

A fault the controller cannot isolate it to a single module. An example would be
the absence of every I/O module in a termination assembly group.

The System Healthy LED on each processor module will show red.

Module Fault

The controller indicates a module fault when it detects a fault and can isolate it to the hardware of a
particular module. The Healthy LED on the faulty module will show red and the System Healthy LED
on each processor module will also show red.

Channel Fault

The controller indicates a channel fault when it detects a fault and can isolate it to a hardware fault on
a specific channel of a single I/O module. The controller always reports a channel fault as a module
fault as well. This means that the Channel LED will show red, the Healthy LED of the I/O module will
show red and the System Healthy LED on each processor module will also show red.

Field Fault

The AADvance controller indicates a field fault when it detects a fault and can isolate it to a field
condition or a field device. Examples are an open circuit field connection or an out-of-range signal. The
Channel LED on the relevant I/O module will show amber.