Rockwell Automation AADvance Controller Troubleshooting and Maintenance Manual User Manual
Page 32

3-10
Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:
Troubleshooting and Maintenance Manual (AADvance
Controller)
an operating controller has at least one variable being locked/forced
Aux
This LED is controlled by the application. The application can turn it on/off
and any colour except when the processor is in the Recovery Mode and
the application is stopped
OFF
No power and stays off while the module is booting up (10 to 20
seconds), or under application control
GREEN
Under application control
AMBER
Module is in the Recovery Mode
or
under application control
Serial 1 and 2
Provides an indication of serial port activity
OFF
No power and stays off while the module is booting up (10 to 20 seconds)
RED
Pulse stretched Tx
GREEN
Pulse stretched Rx
AMBER
Tx and Rx activity in close proximity
Ethernet 1 and 2
Provides an indication of Ethernet port activity
OFF
No power and stays off while the module is booting up (10 to 20 seconds)
GREEN
Ethernet link present
AMBER
Tx or Rx activity
Note: When inserting more than one processor module they MUST be inserted one at a time and the
module allowed to educate (in the case of a 2nd and 3rd processor).