Rockwell Automation AADvance Controller Troubleshooting and Maintenance Manual User Manual

Page 52

Advertising
background image

4-8

Document: 553634

(ICSTT-RM406F_EN_P) Issue: 089:

Troubleshooting and Maintenance Manual (AADvance
Controller)

Step Task

Ready

GREEN

Run

RED to GREEN (Flashes GREEN as the module educates)

System Healthy GREEN

Force

GREEN

Aux

Off (Application Dependent)

Serial 1

Dependent on data connection

Serial 2

Dependent on data connection

Ethernet 1

Dependent on data connection

Ethernet 2

Dependent on data connection

Table 5:

Procedure for Installation of a 2nd and 3rd Processor

Note: The second and third processor modules must be programmed with the same firmware as the
first processor. Check the firmware revision on the labels and if required use the procedure in the
Configuration Guide. If the firmware revision is different to the first processor module you can
download the latest firmware build to all the processor modules using the ControlFLASH utility.

When inserting a second and third processor module they MUST be inserted one at a time and
allowed to educate before inserting the next one.

Step Task

1.

Place the processor module on slot B on the Processor Base Unit connectors and push the
module home until the connectors are fully mated. Turn the locking screw with a flat bladed

screwdriver to lock the module in position.

All the Module LEDs are OFF until the module is installed. As soon as the module receives
power it will boot up then educate and display the following indications:

Healthy

Flashes RED for a second then goes GREEN as the module boots up (10
to 20 seconds)

Ready

Will remain OFF as the module boots up (10 - 20 seconds) then goes

RED for 10 secs then flashes GREEN as it educates and finally it goes to
steady GREEN

Run

Will remain OFF as the module boots up (10 - 20 seconds) then goes

RED until educated and then it goes AMBER

System Healthy

Will remain OFF as the Module boots up (10 to 20 seconds) then goes

Advertising