PowerFlex® 700S and 700H Frame 12 Replacement Power Structures

13

Installation on a Grounded B Phase Delta System

If you are installing a drive on a grounded B phase Delta system, you:

Must move the common mode jumper to the disconnected position -
refer to

Move the Common Mode Jumper to the Disconnected

Position on page 14

.

Must insulate terminal X4 on the Rectifier circuit board- refer to

Insulate

Terminal X4 on the Rectifier Circuit Board on page 15

.

Must disconnect the small capacitors from the input terminals - refer to

Disconnect the Small Capacitors from the Input Terminals on page 16

.

Note:

Refer to Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives - Installation Instructions
,
publication DRIVES-IN001…, for additional information on an
ungrounded distribution system or high resistive ground
installation.

Figure 2 Common Mode Jumper and Rectifier Circuit Board Location

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

Common
Mode jumper

Rectifier Circuit Board

Front View
of Assembly

There is one jumper located on
each Rectifying Module. The
Rectifying Modules are located on
the upper-right side of the right side
power stack of in each enclosure of
the drive’s power structure.

Control Frame not shown for clarity only