PowerFlex® 700S and 700H Frame 12 Replacement Power Structures

7

4. Carefully disconnect the fiber-optic cables from sockets along the front

of the ASIC board, and carefully set them aside.

5. Disconnect the other cables from the sockets on the front of the ASIC

board, and set them aside.

6. If you are replacing a power structure on a PowerFlex 700S drive,

disconnect the cable from connector J8 and the fiber optic connections,
J4 and J5, from the Power Supply Voltage Feedback board on the power
structure in the left-hand enclosure.

!

ATTENTION: Hazard of permanent eye damage exists when
using optical transmission equipment. This product emits intense
light and invisible radiation. Do not look into fiber-optic ports or
fiber-optic cable connectors.

!

ATTENTION: The sheet metal cover and mounting screws on
the ASIC Board located on the power structure are energized at
(-) DC bus potential high voltage. Risk of electrical shock, injury,
or death exists if someone comes in contact with the assembly.

H11

H12

H13

H8

H9

H10

X6

X9

X15

X3

X4

X5

X2

X1

H4

H5

H6

H1

H2

H3

H7

X26

X11

Fiber Optic ports

Connects to X50
terminal block for
pre-charge circuitry on
DC Input drives

Connects to DC Bus

J4 J5

J8