Installing the XM-220 Dual Speed Module 33

Figure 2.22 Magnetic Pickup to Channel 2 Wiring

Connecting a TTL Output Device

The figures below show the wiring of a TTL output device to the terminal
base unit.

Signal Common

Channel 2 Input Signal

Shield

17

1

38

Cable shield not
connected at this end

T Y P I C A L W I R I N G F O R M A G N E T I C P I C K U P S E N S O R

T O X M - 2 2 0 D U A L S P E E D M O D U L E C H A N N E L 1

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the terminal base
and not at the transducer. Any convenient Chassis terminal
may be used (see Terminal Block Assignments on page 18).

IMPORTANT

The internal transducer power supply is providing power to
the TTL device.