Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual

Page 74

Advertising
background image

Publication GMSI10-UM004B-EN-P - May 2010

66 Specifications

Inputs

2 Tachometer Inputs

Input Impedance

Speed/Frequency Range

Speed Measurement Error

±25V (50V maximum peak to peak)
Eddy current transducer signals
Magnetic pickups
TTL output devices

120k ohms minimum

1 to 1,200,000 RPM
0.0167 to 20,000 Hz

1 to 240 RPM ±0.2 RPM
241 to 12,000 RPM ±2 RPM
12,001 to 20,400 RPM ±5 RPM
20,401 to 120,000 RPM ±20 RPM
120,001 to 360,000 RPM ±50 RPM
360,001 to 1,200,000 RPM ±160 RPM

Outputs

4-20mA Outputs

Buffered Outputs

Each output is independently programmed
to represent speed or acceleration, from
either channel.
Two isolated outputs
300 ohm max load

1 active buffer per input channel
Output range configurable by wiring:
-24 to +9V
-5 to +24V
-5 to +9V
Third buffered output available when the
module is configured for single redundant
channel mode. Outputs a CMOS (0 to 5
volts) level square-wave that corresponds
to the active input signal.

Sensor Fault Detection

Eddy Current Transducer

Magnetic Pickups

Bias voltage is compared with the fault
limits.

A current source is available for biasing
passive magnetic pickups to detect open or
short circuits.

Indicators

7 LEDs Module Status - red/green

Network Status - red/green
Channel 1 Status - yellow/red
Channel 2 Status - yellow/red
Startup -yellow
Relay - red
AUX - reserved for future use

Measured Units

RPM
Direction of Rotation
Acceleration in RPM/Minute

XM-220 Technical Specifications

Product Feature

Specification

Advertising