Sets the relay activation logic.
•
A or B - Relay is activated when either Alarm A or
Alarm B meets or exceeds the selected Alarm
Status condition(s).
•
A and B - Relay is activated when both Alarm A
and Alarm B meet or exceed the selected Alarm
Status condition(s).
•
A Only - Relay is activated when Alarm A meets
or exceeds the selected Alarm Status
condition(s).
Options: A only
A or B
A and B
Sets the alarm(s) that the relay will monitor. The
alarm must be from the same device as the relay.
When the Activation Logic is set to "A and B" or "A
or B," you can select an alarm in both Alarm A and
Alarm B. The system monitors both alarms. When
the Activation Logic is set to "A Only," you can
select only an alarm in Alarm A.
Options: Channel 1 Speed
Channel 2 Speed
Channel 1 Acceleration
Channel 2 Acceleration
Channel 1 Zero Speed
Channel 2 Zero Speed
Channel 1 Locked Rotor
Channel 2 Locked Rotor
Note: You can only select an alarm
that is enabled.
Relay Parameters
Parameter Name
Description
Options/Comments
XM Configuration
Utility
EDS File
Activation Logic
Logic
XM Configuration
Utility
EDS File
Alarm A/B
Alarm
Identifier
A/B