CE Filter Kits for the VSM500 Integrated Drive/Motor

Installing the Internal Mount CE Filter Kit

Step 1. Remove the cover of the VSM500 unit by loosening the four cover screws. The display ribbon cable is

designed to disconnect from the main unit when the cover is removed.

Step 2. Mount the CE filter as shown in figure 1 below using the screws and lock washers provided.

Step 3. Connect the incoming AC supply line to the CE filter as shown in figure 2 and figure 3.

Important: The filter may cause ground leakage currents. Therefore, a solid ground connection must be

provided as shown in figure 2.

!

ATTENTION: To prevent electrical shock, disconnect the power source before installing or
servicing the unit. Failure to observe these precautions could result in severe bodily injury or loss
of life.

ATTENTION: After disconnecting input power, wait five minutes and check with voltmeter to
assure that DC bus capacitors are discharged. The voltmeter should read zero volts. Failure to
observe these precautions could result in severe bodily injury or loss of life.

Figure 1 – Mounting the Internal CE Filter Kit

1.46 Nm

(13 in-lb)

2.6 Nm

(23 in-lb)