CE Filter Kits for the VSM500 Integrated Drive/Motor
3
Step 4. Connect the power wires from the CE filter to the VSM500 unit as shown in figure 3 (three-phase unit
shown).
Step 5. Reconnect the display ribbon cable and reinstall the unit cover.
!
ATTENTION: RFI filters can only be used with AC supplies that are nominally balanced with
respect to ground. In some installations, three-phase supplies are occasionally connected in a
3-wire configuration with one phase grounded (Grounded Delta). The filter must not be used in
Grounded Delta supplies. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
Figure 2 – Wiring the Internal Mount CE Kit
Figure 3 – Wiring the CE Filter to the VSM500 Drive/Motor
!
ATTENTION: The cover screws must be securely tightened in order to properly ground the cover.
Verify that all four cover screws are tight before applying power to the unit. Failure to observe
this precaution could result in severe bodily injury or loss of life.
Conduit/4-Wire Cable
Nearest Building Structure Steel
PE
VSM500 Integrated Drive/Motor
L1
IN
L2
IN
L3
IN
W3
OUT
W2
OUT
W1
OUT
T/L3
S/L2
R/L1
CE Filter
DC+
DC-
DBR
T/L3
S/L2
R/L1
PE
L3
L2
L1
1.3 Nm
(12 in-lb)
1.3 Nm
(12 in-lb)