CE Filter Kits for the VSM500 Integrated Drive/Motor

5

Step 3. Connect the input power wires to the CE filter as shown in figure 6 (three-phase unit shown).

!

ATTENTION: RFI filters can only be used with AC supplies that are nominally balanced with
respect to ground. In some installations, three-phase supplies are occasionally connected in a
3-wire configuration with one phase grounded (Grounded Delta). The filter must not be used in
Grounded Delta supplies. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.

Figure 5 – Wiring the External Mount CE Filter

Figure 6 – Wiring the Input Power Leads to the CE Filter

Conduit/4-Wire Cable

Nearest Building Structure Steel

PE

VSM500 Integrated Drive/Motor

L1

IN

L2

IN

L3

IN

L3'

OUT

L2'

OUT

L1'

OUT

T/L3

PE

PE

S/L2

R/L1

CE Filter

0.3-0.8 Nm

(3-7 in-lb)

2.8 Nm

(25 in-lb)

L1 L2 L3 PE

IN

OUT

Incoming

AC Power

To VSM500 Integrated Drive/Motor

AC Input Terminals

1.3 Nm

(12 in-lb)