Rockwell Automation VSM-CE-1l, 3l, 3E Integrated Drive/Motor CE Filter Kits User Manual
Page 5

CE Filter Kits for the VSM500 Integrated Drive/Motor
5
Step 3. Connect the input power wires to the CE filter as shown in figure 6 (three-phase unit shown).
!
ATTENTION: RFI filters can only be used with AC supplies that are nominally balanced with
respect to ground. In some installations, three-phase supplies are occasionally connected in a
3-wire configuration with one phase grounded (Grounded Delta). The filter must not be used in
Grounded Delta supplies. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
Figure 5 – Wiring the External Mount CE Filter
Figure 6 – Wiring the Input Power Leads to the CE Filter
Conduit/4-Wire Cable
Nearest Building Structure Steel
PE
VSM500 Integrated Drive/Motor
L1
IN
L2
IN
L3
IN
L3'
OUT
L2'
OUT
L1'
OUT
T/L3
PE
PE
S/L2
R/L1
CE Filter
0.3-0.8 Nm
(3-7 in-lb)
2.8 Nm
(25 in-lb)
L1 L2 L3 PE
IN
OUT
Incoming
AC Power
To VSM500 Integrated Drive/Motor
AC Input Terminals
1.3 Nm
(12 in-lb)