Installing the external mount ce filter kit – Rockwell Automation VSM-CE-1l, 3l, 3E Integrated Drive/Motor CE Filter Kits User Manual
Page 4

4
CE Filter Kits for the VSM500 Integrated Drive/Motor
Installing the External Mount CE Filter Kit
Step 1. Mount the enclosed CE filter as shown in figure 4.
The cable length from the filter to the drive/motor must be less than 3 meters (10 feet).
Step 2. Connect the filter between the incoming AC supply line and the drive input terminals as shown in
figure 5 and figure 6.
Important: The filter may cause ground leakage currents. Therefore, a solid ground connection must be
provided as shown in figure 5.
!
ATTENTION: To prevent electrical shock, disconnect the power source before installing or
servicing the unit.
ATTENTION: The National Codes and standards (NEC, VDE, BSI, etc.) and local codes outline
provisions for safely installing electrical equipment. Installation must comply with specifications
regarding wire types, conductor sizes, branch circuit protection, and disconnect devices. Failure
to do so may result in personal injury and/or equipment damage.
Figure 4 – Mounting the Enclosed CE Filter
152.0
(6.0)
29.0
(1.13)
10.0
(0.38)
273.0
(10.75)
225.0
(8.87)
292.0
(11.5)
113.0
(4.46)
3.0
(0.10)
mm
(in)
Front View
Side View