However, care should be exercised in applying the module to 
small load devices. 
Off-state test current (Leakage current ) of the output circuit 
may prevent some load devices from turning off completely. 
Table 2 lists the off-state voltages (worst case) for various load 
ratings and module configurations. These should be 
compared to the “guaranteed off” voltage for the load device 
being applied. 
Table 2. Off-State Voltage Ratings.
Load
OFF State Voltage (nominal field voltage and shorted switch)
Rating
T7481/81A (24 Vdc)
T7484 (110 Vac)
T7488/88A (120 Vdc)
(mA)
Single
Dual
Single
Dual
Single
Dual
5
na
2.6
na
3.7
na
na
na
12.8
na
18.3
10
na
1.4
na
2.0
na
na
na
6.8
na
9.9
20
4.7
.71
6.4
1.0
23.5
31.8
na.
3.5
na
5.2
35
3.0
.41
4.1
.6
14.8
20.8
17.5
2.0
24.4
3.0
50
2.2
.29
3.1
.43
10.8
15.5
12.8
1.4
18.2
2.1
100
1.2
.15
1.7
.21
5.7
8.4
6.7.
.71
9.8
1.0
Field Wiring
Field wiring terminal blocks on the I/O chassis are used to 
connect power sources and loads to the module. The terminal 
blocks are located directly above and below the slot where the 
module is installed. Each terminal block consists of ten #6 
wire clamp screw terminals capable of holding two 12 AWG 
wires. 
Each module has separate power terminals for each output 
group (group 1: channels 1-8, group 2: channels 9-16). The 
two groups are electrically isolated from each other. Figure 6 
shows the proper field wiring for a single module and Figure 7 
shows the field wiring for fault tolerant modules connected in 
parallel. 
This module does not require a return connection from the 
field power source. Do not connect any field wiring to 
terminals A and D. 