Rockwell Automation T7488/T7488A ICS Regent+Plus Monitored Guarded Output Modules User Manual
Page 3
 
Monitored Guarded Output Modules (T7481/81A, 84 and 88/88A)
 
P D - 6 0 3 3 M a r - 0 6  (Issue 2) 
3
The processor modules send triplicated write data commands 
over the I/O Safetybus to the monitored Guarded output 
module. Onboard the output module the triplicated data are 
routed to two independent voters which provide voted data to 
associated field programmable gate arrays (FPGA). Each 
FPGA independently operates one of the two output control 
switches. The two output switches are connected in series with 
the load. 
When both output switches are on, current will flow through 
the output and energize a field load. If either switch is off, 
current will not flow through the output and the load will be 
de-energized. This combination of series output switches and 
independent drive signals produces fail-safe activation of the 
load. Single failures can only affect one of the output drive 
signals or switches. A single failure will result in either 
continued correct control or a fail-safe output as shown in 
Table 1. 
Table 1. Output States After Switch Failure.
 
 
Case
Commanded
Output State
Switch
Failed
State
Actual
Output
to Load
 
 
Remarks
1
On
On
On
Continued correct control. 
Automatic testing detects 
stuck-on switch. If output is 
subsequently commanded 
off, output will turn off. 
2
On
Off
Off
Fail-safe output. Automatic 
testing detects stuck-off 
switch. 
3
Off
On
Off
Continued correct control. 
Automatic testing detects 
stuck-on switch. If output is 
subsequently commanded 
on, output will turn on. 
4
Off
Off
Off
Fail-safe output. Automatic 
testing detects stuck-off 
switch. If output is subse-
quently commanded on, 
output will remain off. 
To achieve fault tolerance, two monitored Guarded output 
modules are used with their outputs connected in parallel. 
This configuration provides for continued correct control even