Monitored Guarded Output Modules (T7481/81A, 84, and 88/88A)
 
6  (Issue 2)
Industrial Control Services
monitored by the application program or external operator 
interface equipment to dispatch maintenance personnel to 
correct the field connection problem. 
Field faults such as open load, shorted load, blown fuse and 
absence of field power, will mask an output switch fault. When 
load/fuse faults are detected, they should be repaired as soon 
as possible. 
If the health of spare, unused output points is important, then 
a minimum load device should be connected to these points. 
Front Panel
Figure 2 shows the physical features of the monitored 
Guarded output modules. The front panel of each module 
contains a module active and fault status indicator, a 
shutdown indicator, as well as output fuses, output status 
indicators and load/fuse fault indicators for the output 
circuits. 
Active/Fault Status Indicators
These green and red LEDs indicate the overall health of the 
module and output circuits. During normal operation, the 
green ACTIVE indicator flashes at the controller's scan rate. 
If a module fault is detected, the red FAULT indicator turns 
on and the green ACTIVE indicator turns off. 
Shutdown Indicator
Upon loss of communications with the controller, output 
modules enter either a shutdown or hold fault mode. If the I/O 
unit is set to shutdown, the red SHUTDOWN
indicator will
turn on when communications with the controller are lost. If 
the I/O unit is set to hold, the SHUTDOWN indicator will 
always be off (see page 16, Fault Mode Jumper). 