Rockwell Automation T7488/T7488A ICS Regent+Plus Monitored Guarded Output Modules User Manual
Page 5
 
Monitored Guarded Output Modules (T7481/81A, 84 and 88/88A)
 
P D - 6 0 3 3 M a r - 0 6  (Issue 2) 
5
During testing, the output state is changed; outputs that are 
on are turned off and outputs that are off are turned on. 
When two monitored guarded output modules are wired in 
parallel for fault tolerance, the output circuit testing of the 
dual modules is coordinated. The test coordination is 
automatically performed by the system when the modules are 
properly configured for dual mode (see Configuration, starting 
on page 17). When dual modules are tested, the second 
module’s outputs are turned off momentarily while the first 
module’s outputs are tested. Subsequently, the first module’s 
outputs are turned off while second module’s outputs are 
tested. 
When an output switch is tested, the test pulse duration is 
nominally 250 msec, and is insufficient to affect the state of 
most field loads. With modules configured in dual mode, the 
maximum test pulse may be 425 msec if one module has a 
switch failure. The output circuit test interval will range from 
1 to 60 seconds, depending on the quantity of I/O configured 
in the system. 
If an output switch doesn’t change state when tested, an 
output switch fault is detected. An output switch failure is 
annunciated as a module fault. An I/O module fault is 
indicated by the module FAULT LED on the module, the red 
I/O fault LEDs on the processor modules and the system 
control relay fault bit for the module assembly and slot. 
Load and Fuse Monitoring and Testing
During output switch testing, the module also monitors the 
change in current flow in the field power for the outputs. The 
sensed state changes of the output switches and the field 
power current are reported back to the processor modules. 
The triplicated processor modules use this information to 
identify if an open load, shorted load or blown fuse condition 
exists. 
Any of these load/fuse fault conditions are annunciated via 
the LOAD/FUSE fault LEDs on the face of the module and the 
Fault Name variables configured for each point. Load/Fuse 
faults are not reported as module faults and so do not turn on 
the red Module FAULT LED or associated system variable 
control relay fault bit. The Fault Name variables should be