Monitored Guarded Output Modules (T7481/81A, 84 and 88/88A)
 
P D - 6 0 3 3 M a r - 0 6  (Issue 2) 
19
Figure 10. Defining the Guarded Output Module Definition.
If you do not configure the modules for Dual Mode then the 
output testing performed on the modules will not be 
coordinated and each of the modules wired in parallel will 
report a fault. 
For the T3484, 110 VAC Monitored Guarded Output Module 
you must also select the line frequency of the field power 
supply. In the Line Frequency drop-down list, select either 
50 Hz or 60 Hz. 
4) Edit each point:
Choose Edit from the Module Definition dialog box to define a 
name and description for each output point. In the Monitored 
Guarded Output Point dialog, enter names and values for the 
configuration fields as described below. 
Note:
Note: