Safety considerations, Specifications – Rockwell Automation T7488/T7488A ICS Regent+Plus Monitored Guarded Output Modules User Manual
Page 23
 
Monitored Guarded Output Modules (T7481/81A, 84 and 88/88A)
 
P D - 6 0 3 3 M a r - 0 6  (Issue 2) 
23
Safety Considerations
The Monitored Guarded output modules are TÜV certified to 
Risk Class 5 for safety critical outputs. The modules are 
approved for de-energize to trip safety critical outputs in 
single or dual module configurations. 
The modules are also approved for energize to trip safety 
critical outputs in dual module configuration, but only if the 
fault name variables are configured and used to automatically 
alarm and annunciate the detection of load/fuse faults to plant 
operations personnel. 
Specifications
Safetybus Power
1.5 load units
Number of Outputs
16 circuits divided into two 
groups of 8 circuits each 
T7481 (81A)
T7484
T7488 (88A)
Voltage Range
18 to 36 VDC
90 to 130 VAC
95 to 140 VDC
Frequency
N/A
47 to 63 Hz
N/A
Load Current
(0 to 40
°
C)
derating
(at 60
°
C)
2 amp
1.5 amp
0.7 amp
0.5 amp
1.0 amp
0.75 amp
Minimum Load
20 mA ( 5mA)
20 mA
35 mA (5mA)
On State Drop
1.0 V, maximum
2.5 V, maximum 2.0 V, maximum
Surge Current
incandescent,
capacitive loads:
inductive loads:
3.5 amps, peak
7 amps for 
20 msec 
3.5 amps, peak
3 amps for 
20 msec 
3.5 amps, peak
3 amps for 20 msec
Output Leakage
single, fail-safe
module:
dual, fault-tolerant
modules:
5 mA, ( 700ua) 
maximum 
7.5 mA, (1 mA) 
maximum 
5.5 mA, 
maximum 
8.5 mA, 
maximum 
5.5 mA, (700ua) 
maximum 
8.5 mA, (1 mA) 
maximum 
T7481/81A
T7484
T7488/88A