Calculated Industries 5065 User Manual

Page 14

Advertising
background image

User’s Guide — 9

Second Press

If a wire length has been entered, the sec-
ond press displays the smaller of the two
wire sizes. If not solving for Voltage drop
wire size, then displays the maximum
ampacity.

Third Press

Displays the wire size in Circular Mils.
Displays: CMIL

Fourth Press

If a wire length has been entered, displays
the minimum wire ampacity rating. If no
wire length has been entered, displays the
NEC table referenced for the calculation.
Displays: NEC 310.16

S w

125% Ampacity

Used for motor wire sizing when the wire
must not exceed 80% of its rated ampacity
(125%A). This keystroke calculates wire
size based on 125% of the entered or cal-
culated Amps value. Displays: 125%

P

Parallel Size

Used to find the size of parallel conductors
using amperage and an entered quantity of
wires. Parallel wire size calculations small-
er than 1/0 are displayed as “none” (display
shows “nonE”) as the NEC does not allow
parallel wire runs smaller than 1/0.

First Press

When preceded by a number, calcu-
lates the applicable wire size for that
quantity of wires in parallel.
Displays: PAR WIRE SIZE

(Cont’d)