User’s Guide — 13

Fourth Press

Displays the NEC table referenced for
the calculation. Displays: NEC 250.66

S G

Equipment Ground (EqGrnd)

This function uses NEC Table 250-122
to calculate the minimum equipment
grounding conductor size, given an
entered amperage rating or setting for a
over-current device up line (e.g., 300

S G

).

NOTE: This function deviates from the
NEC Table 250-122 in that 1250 MCM
AL is used instead of 1200 as specified
in NEC Table 250-122.

First Press

Displays the copper grounding conduc-
tor size for the entered Amp rating.
Displays: EQPG WIRE SIZE CU

Second Press

Displays the aluminum grounding conduc-
tor size. Displays: EQPG WIRE SIZE AL

Third Press

Displays the NEC table referenced for
the calculation. Displays: NEC 250.122