54 — ElectriCalc Pro

Finding Number of Wires in
Existing Conduit — Same Size,
Various Types

Find the maximum number of #10 THHN
copper wires that can be pulled through an
existing 3 Inch EMT conduit. How many
XHHW wires? How many THW wires?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Enter cond. type

1 S C EMT nonE

COND

Enter wire size*

1 0 w AWG 10 CU

WIRE SIZE

Enter conduit size

3 C

EMT 3.00 in

COND SIZE

Find max THHN #

·

THHN 167.

TTL WIRES

Find max XHHW#

Å

XHHW 145.

TTL WIRES

Find max THW #

THW 145.

TTL WIRES

* Wire size can also be entered in Circular
Mils (e.g.,

1 0 3 8 0 w

enters

10,380 CMILs and displays 10 AWG wire
size).