Equipment grounding conductor wire size – Calculated Industries 5065 User Manual

Page 53

Advertising
background image

48 — ElectriCalc Pro

The

S G

keystroke can be used

to find the grounding conductor size for
raceways and “over-current devices in
circuit ahead” equipment. The calcula-
tor uses the displayed amperage value
to solve for the equipment grounding
conductor based on NEC Table
250-122.

Find the equipment grounding conduc-
tor size required when the circuit-
breaker is rated at 45 Amps and 90°
copper is being used in the installation.
What is the equivalent aluminum size?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 90º C

S 9

3Ø 90 Cu 0.

Enter Amp rating

4 5 A

AMPS 45.

Find equipment

ground wire size

S G

EQPG 10 CU

WIRE SIZE

Find aluminum size

G

EQPG 8 AL

WIRE SIZE

Display NEC Table

G

NEC 250.122

Reset to 60˚C

S 6 o 3Ø 60 Cu 0.

and Clear

Equipment Grounding
Conductor Wire Size