Ampacity wire sizing, Wire sizing based on insulation rating – Calculated Industries 5065 User Manual
Page 39

34 — ElectriCalc Pro
The required wire size of a service con-
ductor can be determined based on the
specified electrical requirements and the
w
key. The wire size is automatically
recalculated whenever the wire insulation
(temperature) ratings or wire material (cop-
per or aluminum) types are revised. Wire
sizing is based on the requirements
defined in NEC Tables 310-16 and 310-17.
Wire Sizing Based on
Insulation Rating
Wiring is being installed in a 240 Volt,
single-phase system rated at 30 kVA.
What is the wire size needed if you use
60°C copper wire?
Steps
Keystrokes
Display
Clear calculator
o o
0.
Set to 1-phase
S 1
1 PH
Enter kVA
3 0 K V KVA 30.
Enter Volts
2 4 0 U VOLT 240.
Find Amps
A
AMPS 125.
Find wire size
w
AWG 0 CU
WIRE SIZE
Display Wire
Ampacity
w
0
125.0 Cu WIRE A
Display CMIL
w CMIL 105,600 WIRE
Display NEC Table
w
NEC 310.16
Ampacity Wire Sizing