Finding Three-Phase
Voltage Drop

A 20 Amp, three-phase load is being fed
by a 230 Volt source located 150 Feet
away. The installation specifications
require 75°C #10 THW stranded copper
conductor. What is the Voltage drop on
this branch circuit?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 75°C

S 7

3Ø 75 Cu 0.

Set to 3-phase

S 3

3Ø 75 Cu 3 PH

Enter Amps

2 0 A

AMPS 20.

Enter Volts

2 3 0 U VOLT 230.

Enter Length(feet)

1 5 0 l FEET 150.

Find VD wire size

w

AWG 10 CU

VD WIRE SIZE

Solve volt. drop

v

DROP 6.4 V

Solve % v.drop

v

DROP 2.8 V %