Finding Voltage Drop Distance

How far from a three-phase 240 Volt
source can you install a 15 Amp load
using 60°C #10 copper branch circuit
conductors? Assume a 3% allowable
Voltage drop.

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 60°C

S 6

3Ø 60 Cu 0.

Enter Amps

1 5 A

AMPS 15.

Enter Volts

2 4 0 U VOLT 240.

Enter wire size*

1 0 w

AWG 10 Cu

WIRE SIZE

Enter 3% VD

3 v

DROP 3.0 V %

Find distance

l

FEET 234.86987

Find actual

Voltage drop

v

DROP 7.2 V

Find % v.drop

v

DROP 3.0 V %

* Wire size can also be entered in Circular
Mils

(e.g.,

1 0 3 8 0 w

enters

10,380 CMILs and displays 10 AWG
wire size).
NOTE: The calculator automatically
makes adjustments for resistance using
NEC Chapter 9, Table 8, if the insulation
type is other than 75°C.