Ultra-cut 300 xt – Tweco 300 XT Ultra-Cut Plasma Cutting System User Manual

Page 167

Advertising
background image

ULTRA-CUT 300 XT

Manual 0�5�7�

PPENDIX

�61

Troubleshooting:

1. If System Bias board has either the wrong jumper or is defective it will call out the first inverter section, code

�31, because all the inverters won’t match the incorrect signal and 1 is checked first.

a. For the jumper Wire #�8 should be connected from J61�1 to:

i. J61�� for �08��30 VC

ii. J61�3 for �00 VC

iii. J61�� for �80 VC

Check for proper connection and continuity.

b. System Bias may be defective reporting the wrong voltage ID. On the output of the System Bias board

at J6� measure relative to TP1 or ( J6��8, ��VDC_RET) to J6��1� for signal /VC_IDb and J6��1� for

signal /VC_IDBb. The � signals should read according to this table. “0” = 10�1�V; “1” = ��V.

signal

�30V �00V �80V ERR

/VC_IDb

0

1

0

1

/VC_IDBb

0

0

1

1

�. Defective inverter, ribbon cable or CCM.

a. On the inverter section swap the ribbon cable of the inverter section whose fault was indicated with that

of a different inverter section. If fault remains unchanged, still calls out the original inverter section, the

problem is with either ribbon cable or CCM. If fault changes to the different section, the one the ribbon

cable was swapped with, then it’s the inverter that’s defective.

b. If the fault remained unchanged in Step , on the inverter end, put the ribbon cables back in their original

positions. Now swap suspect ribbon cable with another one on the CCM. If the fault now moves to a

different section it’s the ribbon cable. If it remains with the original section the problem is the CCM.

237

Too Few Inverters Found

There must be a minimum of � inverter sections present to operate. We know the ribbon cable for inverter sec�

tion 1 is connected or else we would have code ���. During the power up sequence, before power is connected

to the inverters, the CCM does a continuity test through the ribbon cable to see if an inverter is connected. If it

doesn’t see continuity with at least one other inverter it assumes none are connected.

Possible causes:

• Ribbon cable disconnected or defective.
• Inverter defective
• CCM defective.

Troubleshooting:

1. Check that all cables are connected, latches locked down, at both the inverter and CCM ends.

�. If this fault occurs it’s most likely on a 100 unit which only has one section (1B) in addition to the 1 sec�

tion. If there were � or more additional sections it’s extremely unlikely all ribbon cables or CCM connectors

would be defective.

a. Swap the ribbon cables of the inverter section 1 and 1B. If fault remains unchanged, still �37, problem

is with either ribbon cable or the CCM. If fault changes from �37 to ��� indicating inverter 1 missing,

then it’s the inverter that’s defective.

b. If the fault remained unchanged in step a., on the inverter end put the ribbon cables back in their original

positions. Now swap suspect ribbon cables on the CCM. If the fault now changes it’s the ribbon cable.

If it remains the same it is the CCM.

c. If there are � or more ribbon cables in addition to the one on section 1 then CCM is seeing none of them

connected which indicates the CCM is faulty.

Advertising