Viking Pump UDF400: DFO Start-UP Guide User Manual

Page 4

Advertising
background image

Viking Duplex Fuel Oil Package

Field Start-Up Guide

Bulletin:

Issue:

Page:

UDF400
2-Oct-06
3

























Main Disconnect Switches “ON-OFF”

“HAND-OFF-AUTO” Switch for P2

“HAND-OFF-AUTO” Switch for P1

“P1-AUTO-P2”

“RUN” Green Pilot Light

“POWER ON” White Pilot Light

“RUN” Green Pilot Light

Manual “RESET” Button

“LEAD PUMP FAILURE” Red Pilot Light

Fig. 3 – Typical Control Panel Cover


Priming the Duplex Fuel Oil Package:

1.

On the Control Panel make sure both the Main Disconnect “ON-OFF” switches are in the

“OFF” position (power off).

2.

Take a look at the suction gauge to see if there is any pressure on the suction line. If there

is pressure and the application is not a flooded suction the suction line is pressurized.
Carefully remove the drain plug from the basket strainer to release the compressed air.

3.

Turn the four ball valves connected to the pressure gauges (suction & discharge gauges)

to closed position.

4.

Remove the thumbscrew from top of the lid of the basket strainers, rotate the lid counter

clockwise until the pin hits and stops, and then remove lid.

5.

Open the suction valves.

6.

Fill the strainers with diesel (the suction valves should be in open position, as you fill one

strainer the liquid level will flow in the other strainer).

7.

Reinstall the lid with the tab of the lid just to the left of the boss with the body, rotate the lid

clockwise until the holes line up, and reinsert the thumbscrew.

8.

Both the suction and discharge ball valves should be in open position.

VIKING PUMP, INC. • A Unit of IDEX Corporation • Cedar Falls, IA 50613 USA