Important – Cleveland Range KEL-25-T User Manual

Page 22

Advertising
background image

3. Pull Pressure Relief Valve (A) open to insure vessel

is not pressurized.

4. Remove Pressure Relief Valve (A).

5. Replace Pressure Relief Valve (A) with Street Elbow (B).

6. Add distilled water (C) through the Street Elbow (B),

using a funnel if necessary. Refer to Distilled Water
Requirements
chart for the proper amount required.

7. Apply a thread sealant (i.e. Teflon tape) to the

Pressure Relief Valve's (A) thread and replace.

8.

Restore power to unit at the fused disconnect switch.

9.

The kettle must now be vented. (Refer to the
KETTLE VENTING INSTRUCTIONS).

A.

*

Remove

Pressure

Relief

Valve

B.

Attach Street

Elbow

C. Fill unit via Street Elbow

*Important-

Pull ring on Pressure Relief Valve

prior to removal to insure vessel is not pressurized.

Pressure Relief Valve/Gauge Assembly Drawing

KETTLE VENTING INSTRUCTIONS

RESERVOIR FILL
PROCEDURES

The kettle's water level must be maintained at the
proper level to submerge the heater elements. Under
normal operating conditions, the sealed water reservoir
should never require the addition of water.

If the red "low water" light comes on during use (while
the kettle is in an upright position), the water level has
reached a critically low level. The low water protection
control has automatically shut off the heater elements.
The following procedure must be completed before
further use:

NOTE: Have a qualified service technician repair the
leakage problem and add water to the unit. Ensure that
the red "low water" light is on when the kettle is upright.
On tilting kettles, it is normal for the red light to come on
when the kettle is in a tilted position, as the elements
are not submerged in water at this point.

DISTILLED WATER REQUIREMENTS

1. Ensure kettle is at room

temperature and pressure
gauge showing zero or less
pressure.

2.

Shut off power to the kettle

at the fused disconnect
switch.

When Red “Low Water

Kettle

Light” comes

Capacity

on, add Distilled Water

25 gallon

1.0 U.S Gallons

30 gallon

1.5 U.S Gallons

40 gallon

2.0 U.S Gallons

60 gallon

2.1 U.S Gallons

80 gallon

2.6 U.S Gallons

100 gallon

2.8 U.S Gallons

1. Turn kettle ON and set

Temperature Control to 10
(Max.), heat the empty kettle
until unit cycles off.

2. Vent kettle by pulling safety

valve ring 8-10 times in short
2-3 second blasts with a 5
second interval between
pulls.

NOTE: If unit cycles ON, stop
venting and wait for kettle to
cycle OFF before continuing.

3. Turn kettle OFF. Add cold

water to kettle until its surface
temperature is below 100°F.
The pressure gauge needle
should be in the green zone,
indicating a vacuum in the
kettle’s jacket.

2

3

5

6

7

8

9

1

4

10

OFF

50

0

100

150

200

250

300

350

400

40

50

60

0

10

20

30

psi

kPa

V

EN

T

A

IR

50

0

100

150

200

250

300

350

400

40

50

60

0

10

20

30

psi

kPa

V

EN

T

A

IR

50

0

100

150

200

250

300

350

400

40

50

60

0

10

20

30

psi

kPa

V

EN

T

A

IR

Pressure

Gauge

Pressure

Relief

Valve

The following venting procedure should be followed when the
Vacuum/Pressure Gauge needle is in the "VENT AIR" zone:

NOTE: Check for and eliminate leaks prior to venting
(See Repairing Leaks in Steam Jacketed Kettle Fittings).

Advertising
This manual is related to the following products: