Configuration test, Vmware vcenter high availability – Dell UPS 4200R User Manual

Page 114

Advertising
background image

Applying Extended Functionality

115

Configuration Test

To test the installation, please perform a power failure on the UPS and check on vSphere client that the

corresponding ESX/ESXi host enters in Maintenance mode after the “Maintenance mode timer.”

VMware vCenter High Availability

After the High Availability (HA) Cluster feature is enabled, VMware disables the automatic startup and

shutdown functionality when a hypervisor is shut down.
Dell MUMC features for HA mode:

• Dell MUMC will continue to move the VM from one server to the others, if all servers are powered by

different UPSs with different power source (see Figure 99).

Figure 99. HA Mode with Dell MUMC

Dell MUMC continues to protect the hypervisor also when power fails.
Due to the deactivation of the automatic startup and shutdown, at the end of utility failure sequence, all

virtual machines will power-off.
To prevent this VM from powering off, you have two solutions:

• Configure the VMware ESX/ESXi nodes in Dell MUMC to shut down the VMs (remote shutdown of

the virtual machine setting).

• Install a Dell MUMC on each VM, even if it is not an optimized solution. You have to take care that

when VMs move, the Dell MUMC still links to the same UPS power source.

NOTE:

For more information about the deactivation of the Automatic Startup/Shutdown when creating a VMware HA

Cluster, refer to “Creating a vSphere HA Cluster” in the links provided by “vSphere SDK for Perl” on page 117.