Environmental

NOTE: When operating in the expanded
temperature range, ambient temperature warnings
may be reported on the LCD and in the System
Event Log.

10% of annual operating hours

5 °C to 40 °C at 5% to 85% RH with 26 °C dew point.

NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to 5
°C or up to 40 °C for a maximum of 10% of its
annual operating hours.

For temperatures between 35 °C and 40 °C, de-rate

maximum allowable dry bulb temperature by 1 °C per

175 m above 950 m (1 °F per 319 ft).

1% of annual operating hours

–5 °C to 45 °C at 5% to 90% RH with 26 °C dew point.

NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to –5
°C or up to 45 °C for a maximum of 1% of its annual
operating hours.

For temperatures between 40 °C and 45 °C, de-rate

maximum allowable dry bulb temperature by 1 °C per

125 m above 950 m (1 °F per 228 ft).

Expanded operating temperature restrictions

Do not perform a cold startup below 5 °C.

Allow processor performance degrade.

Non-redundant power supplies are not

supported.

Non Dell qualified peripheral cards and/or

peripheral cards are not supported.

103