Dell PowerEdge VRTX User Manual

Page 108

Advertising
background image

Error Code

Message Information

PSU0004

Message

The power input for power supply <

number

> is outside of the

allowable range.

LCD Message

Power input for PSU <

number

> is outside of range. Check PSU

cables.

Details

The operating requirements for the power supply may be found in this
manual or on the power supply itself.

Action

Verify the input source is attached to the power supply. Verify the
input power is within the operating requirements for the power
supply.

PSU0005

Message

The power input for power supply <

number

> is outside of the

allowable range, but it is attached to the system.

Details

The operating requirements for the power supply may be found in this
manual or on the power supply itself.

Action

Verify the input power is within the operating requirements for the
power supply.

PSU0006

Message

Power supply <

number

> type mismatch.

LCD Message

Power supply <

number

> is incorrectly configured. Check PSU.

Details

Power supplies should be of the same input type and power rating.

Action

Install matched power supplies and review proper configuration in
this manual.

PSU0007

Message

Power supply <

number

> is operating at 110 volts, and could cause a

circuit breaker fault.

Details

A power supply that is designed to operate at 220V, but is connected
to a 110V power source requires additional current for operation. The
additional current may trip circuit-breakers or cause other electrical
issues with the input source.

Action

Check input power source and cabling. Use recommended input
power. Review this Manual. If the issue persists, see

Getting Help

.

PSU0008

Message

Power supply <

number

> voltage rating does not match the system's

requirements.

Details

The system does not support mixed voltage power supplies.

Action

Install a power supply with the correct voltage rating.

PSU0016

Message

Power supply <

number

> is absent.

108

Advertising