INSTALLATION OF HEATER

ASSEMBLY INTO BACK BOX

1. Re-install fan deck using two screws.

2. Connect field supply wiring to heater pigtail leads (See figure 4).

Connect field ground wire to green ground lead wire.

3. Install front cover. Push on thermostat knob.

CHECK OPERATION AND SET THERMOSTAT

1. Switch on power supply to heater.

2. Rotate thermostat knob fully clockwise. Heating element and fan should

come on, causing warm air to flow from discharge grille.

3. Allow heater to operate until room is comfortable, then rotate thermo-

stat counter-clockwise until thermostat clicks. The unit will continue to

cycle on and off to maintain temperature.

4. Increase or decrease the setting as required until the desired room tem-

perature is maintained.

For best results, the heater should be left “ON” constantly during the

heating season as the thermostat, when properly set, will maintain the

desired room temperature. In the counter-clockwise position, the heater

will remain off. This unit was shipped with a plug button to render the

thermostat tamper resistant. Remove the thermostat knob and insert

plug button in clearance hole guide.

For ceiling mounted units, a remote wall mounted line voltage thermostat

may be installed to control the unit. Follow instructions for the wall ther-

mostat. Turn the thermostat knob on the unit to full clockwise position for

maximum heat, remove the knob and insert plug button in clearance hole

guide. Set your wall thermostat to desired set point.

OPERATION NOTICE

Your heater is equipped with an automatic reset limit control that will

automatically turn the heater OFF to prevent a fire if the heater

overheats. Should this occur, the indicator light will illuminate and will

continue to shine until the limit resets.

SPECIFICATIONS

MODEL

WIRE

NO.

VOLTS

AMPS

WATTS BTU/HR

SIZE

D1012C

120

8.3

1000

3413

14 awg

D1512

120

12.6

1500

5120

12 awg

208

3.6

750

2560

14 awg

D1024C

240

4.2

1000

3413

14 awg

D2024

208

7.2

1500

5120

14 awg

240

8.3

2000

6826

14 awg

To insure proper grounding of heater and prevent a possible electric

shock, the field supply ground wire must be attached to heater green

ground lead wire.

CAUTION

!

To prevent possible wiring damage, cut excess supply wires inside

backbox to provide approximately 6” (152 mm) for connection to

heater leads. After connections are made, make sure connections

are tight and all wiring is positioned away from fan blade and heating

element.

CAUTION

!

THE ILLUMINATED INDICATOR LIGHT SIGNIFIES THE HEATER HAS

BEEN SUBJECTED TO SOME ABNORMAL CONDITION CAUSING IT

TO OVERHEAT. CHECK HEATER TO INSURE THAT IT HAS NOT BEEN

BLOCKED IN ANY MANNER (IF SO, REMOVE BLOCKAGE). IF THERE

IS NO INDICATION OF BLOCKAGE, IT IS RECOMMENDED THAT

HEATER BE CHECKED BY A REPUTABLE ELECTRICIAN OR REPAIR

SERVICE TO INSURE THE HEATER HAS NOT BEEN DAMAGED.

CAUTION

!

IMPORTANT INFORMATION

MODEL

WATTS

AMPS

DATE

VOLTS

PH

Hz

D2024

MM-YY

240/208

1

60

2000/1500

8.3/7.2

Bennettsville, SC 29512 USA