OPERATION INSTRUCTIONS

1. This heater must be properly installed before it is used.

2. Heater must be controlled by a thermostat. If thermostat is

internal factory installed see below. If external thermostat is
provided, refer to the installation and operating instructions
provided with thermostat.

3. When factory thermostat is provided, the control will be locat-

ed inside heater behind grille with access to the thermostat
shaft obtained through the grille louver opening using a small
flat blade screwdriver.

4. On initial start up and check out, before heater is energized,

rotate thermostat shaft to the full counter-clockwise (lowest
heat) setting. Connect power to the heater and check to ver-
ify the heater is not heating. If heating, disconnect and
check wiring.

5. Rotate thermostat shaft to the full clockwise (CW) (max heat)

setting and allow heater to operate for at least 5 minutes and
verify it is heating.

6. Allow heater to operate until room ambient reached desired

comfort level and then slowly rotate thermostat shaft counter-
clockwise (CCW) until you hear or feel a click. This will pro-
vide a set point to allow the thermostat to cycle the heater on
and off to maintain this approximate temperature. Some
slight adjustments may be necessary to fine tune the heater
to provide the most desired room comfort. To increase time
heater stays on and increase the room temperature, slightly
rotate the thermostat in the CW direction. Likewise, to
reduce the room temperature, slightly rotate the thermostat
in the CCW direction.

3

A

B

5” (127mm)

5” (127mm)

5-13/16”

(147mm)

2” (51mm)

2”

(51mm)

K.O.

K.O.

K.O.

2.1”
(53mm)

1.32”

(33mm)

1.32”

Wall

(33.4mm)

10”

(253mm)

3.25”

(82mm)

Bottom View

“N” mounting

holes

7/8” (21mm) x 1-1/8” (27mm) Nested KOs (Qty. 6)

Fig. 1

Dimensions

“N”

Wattage

“A” (Length)

“B”

Holes

500

28” (709mm)

750

36” (912mm)

1000

48” (1216mm)

19” (481mm)

2

1250

60” (1520mm)

16.68” (423mm)

4

1500

72” (1824mm)

20.63” (523mm)

4

2000

96” (2432mm)

21.5” (545mm)

6

2500

120” (3040mm)

27.5” (697mm)

6

Dimensions

Element

GND.

Factory wiring

Field wiring

Power Supply

To other

heater

To other

heater

GND.

Protector

For supply connections use 75˚
copper wire as follows:

Amps

Wire size

12

14 AWG

16

12 AWG

24

10 AWG

35

8 AWG

45

4 AWG

Fig. 2 Wiring Diagram