Operation

NOTE: Air direction settings are shown in Figures 5, 6,

and 7.

NOTE: Cold air will try to escape near floor level. Warm

air will try to penetrate curtain near top of doorway. Air

flow can be controlled by direction of nozzle louvers and

by high/low settings.

Maintenance

WARNING: ALWAYS DISCONNECT POWER SUPPLY
BEFORE SERVICING.

LUBRICATION

Ball bearings are permanently lubricated and require no

further lubrication.

CLEANING

1. The air door cabinet may be wiped off with a damp

cloth. Do not allow motor to get wet. Do not use

solvents or harsh detergents.

NOTE: Keep air intake louvers clear of dirt and dust

accumulation which could affect performance.
2. Check blower wheels for accumulated dirt twice a year

and clean. If disassembly is required, see GENERAL

SERVICING section.

GENERAL SERVICING

WARNING: IF SERVICING IS REQUIRED, IT SHOULD
BE DONE BY QUALIFIED PERSONS ONLY.

WARNING: ALWAYS DISCONNECT POWER SUPPLY
BEFORE SERVICING.

1. Remove motor/blower assembly. All motor/blower

assemblies are designed for easy removal and service

with wing nuts and quick disconnect electrical

connections.

2. Place motor/blower assembly on workbench.
3. To replace blower wheel, remove the three slotted hex

head screws on outer blower ring assembly (See

Figure 9, Replacement Parts Illustration.) The wheel

is held onto shaft by one hex head screws.

IMPORTANT: NOTE POSITION OF WHEELS TO

PREVENT RUBBING WHEN REPLACED.
4. To remove motor:

a. Remove blower wheels. (See Step 3 above.)

b. Remove blower scrolI (six hex head screws).

c. Unscrew and remove motor mounts.

5. Replace motor/blower assembly.

Figure 5 - Desired Air Flow
Adjustment for Temperature and
Humidity Control.

Figure 6 - Desired Air Flow Adjustment
for Insect and Dust Control.

Figure 7 - Desired Air Flow
Adjustment for Freezer and
Cooler Applications.

1. After power has been connected to unit, fans will start.

2. Air direction at outlet can be controlled by adjustable

vanes at the nozzle which compensates for possible

draft conditions.

Advertising
This manual is related to the following products: