Qmark High Velocity Electric Heated User Manual

Page 9

Advertising
background image

* SEE
CHART

PLUG/SOCKET

CONNECTOR

(NO. OF UNITS) X KW LOAD PER UNIT:

480

(3) X 12

(3) X 8

(3) X 8

VOLTS

1 HP

3 HP

00

30

MOTOR CODE

R

L1 L2 L3

G

3

2

1

PL PL PL

R2

R1

R1

R2

FU

T

G

MAIN PANEL

G

HHF

F

CC

FROM MOTOR

YEL

YEL

A1 A2

NO

C

G

HHF

F

CC

FROM MOTOR

YEL

YEL

A1 A2

NO

C

G

FR3

HR3

T1

FR3 HR3

6

PL

HHF

F

CC

FROM MOTOR

YEL

YEL

A1

A2

PDS3

NO

C

FROM HEATER

FROM HEATER

FROM HEATER

BLK

YEL

BLU

T2 T3

FR2

HR2

T1

FR2 HR2

5

PL

T2 T3

FR1

HR1

T1

FR1 HR1

4

PL

T2 T3

PDS2

PDS1

PWB1

CWB2

CABINET COMPONENTS PANEL 1

CWB1

FWB1

CWB3

CABINET COMPONENTS PANEL 2

CWB2

FWB2

CABINET COMPONENTS PANEL 3

CWB3

FWB2

FWB1

G

W

H

F

C

PWB1

LEGEND

A1,A2...................AUTOMATIC RESET PROTECTION
R1......................HEATING RELAY
R2......................FAN RELAY
HR1, HR2, HR3...........HEATING CONTACTORS
FR1, FR2, FR3...........FAN CONTACTORS
T.......................CONTROL TRANSFORMER
FU......................CONTROL FUSE
PL1, PL4, PL6...........PILOT LIGHT, HEAT ON
PL2.....................PILOT LIGHT, POWER ON
PL3.....................PILOT LIGHT, FAN ON
G.......................GROUND LUG
L1L2L3..................POWER TERMINAL BLOCKS
RGWHFC..................CONTROL TERMINAL BLOCKS
HHFFCC..................CONTROL TERMINAL BLOCKS
PWB1....................POWER WIRE BUNDLE (MAIN TO UNIT 1)
FWB1....................FAN CONTACTOR WIRE BUNDLE (FR1 TO UNIT 2)
FWB2....................FAN CONTACTOR WIRE BUNDLE (FR2 TO UNIT 3)
CWB1....................CONTROL WIRE BUNDLE (MAIN TO UNIT 1)
CWB2....................CONTROL WIRE BUNDLE (UNIT 1 TO UNIT 2)
CWB3....................CONTROL WIRE BUNDLE (UNIT 2 TO UNIT 3)
PDS1, PDS2, PPDS3.......PRESSURE DIFFERENTIAL SWITCH

*CONNECTION CHART FOR PRIMARY OF
MULTIPLE TAP TRANSFORMER:

VOLTAGE: CONNECTION:

480 V BLACK AND BLK/RED

R

G

W

THERMOSTAT
(FIELD INSTALLED)

CWB1

DOOR SWITCH
(FIELD INSTALLED)

FIELD WIRING

R1

BLU

L1

L2

L3

L1

L2

L3

L1

L2

L3

WIRING DIAGRAM: 480V - Three cabinets,
8KW and 12KW

* SEE
CHART

PLUG/SOCKET

CONNECTOR

(NO. OF UNITS) X KW LOAD PER UNIT:

208

(2) X 11.25

(2) X 11.25

(2) X 9

(2) X 9

(2) X 6

240

(2) X 15

(2) X 15

(2) X 12

(2) X 12

(2) X 8

VOLTS

1 HP

3 HP

00

30

MOTOR CODE

R

L1 L2 L3

G

3

2

1

PL PL PL

R2

R1

R1

R2

FU

T

G

MAIN PANEL

G

HHF

F

CC

FROM MOTOR

YEL

YEL

A1

A2

NO

C

G

HHF

F

CC

FROM MOTOR

YEL

YEL

A1

A2

NO

C

FROM HEATER

FROM HEATER

BLK

YEL

BLU

FR2

HR2

T1

FR2 HR2

5

PL

T2

T3

FR1

HR1

T1

FR1 HR1

4

PL

T2 T3

PDS2

PDS1

BWB1

CWB2

CABINET COMPONENTS PANEL 1

CWB1

BWB2

CABINET COMPONENTS PANEL 2

CWB2

G

W

H

F

C

BWB1

LEGEND

A1,A2...............AUTOMATIC RESET PROTECTION
R1....................HEATING RELAY
R2....................FAN RELAY
CB1, CB2 ........CIRCUIT BREAKERS
HR1, HR2 ........HEATING CONTACTORS
FR1, FR2.........FAN CONTACTORS
T ......................CONTROL TRANSFORMER
FU....................CONTROL FUSE
PL1, PL4, PL5.PILOT LIGHT, HEAT ON
PL2 ..................PILOT LIGHT, POWER ON
PL3 ..................PILOT LIGHT, FAN ON
G......................GROUND LUG
L1L2L3 ............POWER TERMINAL BLOCKS
RGWHFC ........CONTROL TERMINAL BLOCKS
HHFFCC..........CONTROL TERMINAL BLOCKS
BWB1 ..............C-BREAKER WIRE BUNDLE (BRKR 1 TO UNIT 1)
BWB2 ..............C-BREAKER WIRE BUNDLE (BRKR 2 TO UNIT 2)
CWB1 ..............CONTROL WIRE BUNDLE (MAIN TO UNIT 1)
CWB2 ..............CONTROL WIRE BUNDLE (UNIT 1 TO UNIT 2)
PDS1, PDS2....PRESSURE DIFFERENTIAL SWITCH

*CONNECTION CHART FOR PRIMARY OF
MULTIPLE TAP TRANSFORMER:

VOLTAGE: CONNECTION:
208 V BLACK AND RED
240 V BLACK AND ORANGE

R

G

W

THERMOSTAT
(FIELD INSTALLED)

CWB1

DOOR SWITCH
(FIELD INSTALLED)

FIELD WIRING

CB1

CB2

BWB2

R1

BLU

L1

L2

L3

L1

L2

L3

WIRING DIAGRAM: 240V, 208V - Two cabinets,
8KW, 12KW and 15KW

Advertising