ALARM OPERATIONS

Refer to SWITCH OPTIONS pages

Device features

For LBM models only:

push and hold deadlatch while

performing unit arming test.

Deadlatch detail

Deadlatch

Figure 2

Figure 1

Mortise

Cylinder

Green LED

= On

= Off

PushPad

(LHR shown)

Siren

Red LED

SPECIAL NOTES and DEFINITIONS

1. The door needs to be closed to test the unit.

2. When operating the ON/OFF switch, there is a slight delay.

3. The key is inserted and removed only in the horizontal position (home position).

4. Key function: counter clockwise (CCW) = Armed; clockwise (CW) = Disarmed.

5. Arming delay mode and auto rearm timers vary by order.

6. The power needs to be removed to register changes in the slide switches.

a. Status Indicator (This will affect battery life)

b. Disable Auto Rearm

c. Dis Lo Bat INDicator (EH units only)

UNIT ARMING TEST:

1. Turn key counterclockwise (CCW) (key is removable after rotating back to horizontal position).

2. Red LED will flash twice, then green LED will illuminate for the 15 second delay time, then turn off.

The siren will sound three short beeps indicating the unit is armed.

3. Depress Pushpad (Siren will sound and red LED will illuminate)

4. Turn key clockwise (CW). Turns alarm off.

LOW BATTERY ALERT:

1. Siren will beep and red LED will blink at approximately 45 second intervals when battery is low.

DOGGING FEATURE: (non-fire rated units only)

1. Depress Pushpad.

2. While holding Pushpad depressed, turn key clockwise (CW). Pushpad should remain depressed.

(Key is removable after rotating back to horizontal position)

3. Unit is now disarmed.

STATUS INDICATOR

1. Slide the switch to ON and apply power.

2. If the unit is armed, the red LED will blink every 3 seconds.

3. If the unit is disarmed, the green LED will blink every 3 seconds.

Disable AUTO REARM

1. When the unit is in full alarm and the door closes, the alarm will shut off after 2 minutes.

Care and Maintenance:

The Detex Value Series® devices are designed to provide many years of maintenance free service

under normal usage. Periodically inspect and lubricate the unit to extend its life.