Setback (oat) lockout setup, Staging setup, Valve setup – KMC Controls FlexStat Operation Guide User Manual

Page 10: Advanced) cb (control basic) programs, Advanced) cb (control basic)

Advertising
background image

FlexStat 10

Operation Guide, Rev. R

Setback (OAT) Lockout Setup

SETBACK LOCKOUT

OAT LOCKOUT:

LOCKOUT TEMP: 30° F

ENABLE

Setback OAT lockout is disabled by default. When

enabled, AI4 is configured for OAT and the Lockout

Temp selection appears in the menu. This may be

useful when a system, such as an HPU, may have

difficulty recovering from the unoccupied setpoint to

the occupied setpoint during very cold weather.
NOTE: When enabled, the default value is 30° F

(–1° C) for HPU and 10° F (–12° C) for all

other applications. The value is adjustable

between –50 and 120° F (–45.5 and 49° C).

Staging Setup

STAGING

STG DELAY (MINS):

3

After the first stage starts in multistage heating or

cooling, the default delay time before the second

stage can start is 3 minutes.

Valve Setup

VALVE SETUP

CLG (0–100%):

HTG (0–100%): 0–10V

0–10V

Proportional valves have a 0–10 VDC default for

0–100% open. Change as needed (e.g., 10–2 VDC).

(Advanced) CB (Control Basic) Programs

CB PROGRAMS

PROG1:

PROG2: RUNNING
PROG3: RUNNING
PROG4: RUNNING
PROG5: RUNNING
PROG6: HALTED
PROG7: IDLE

RUNNING

PROGRAM #1

SETPOINTS & MODES
AUTO-RUN: TRUE
CHANGE: READY
STATE: RUNNING
HALT REASON: NORMAL
HALT DESC:
OUT OF SERVICE: FALSE

To halt or load/run the built-in (1–5) and custom

(6–10) Control Basic programs, navigate to the de-

sired line and selection.
If custom Control Basic programs are installed and a

restore to factory settings is performed, all factory

programs are restarted but all custom Control Basic

programs are halted. Change the state of each pro-

gram by loading/running the program from the CB

Programs menu (or BACstage or TotalControl).
If custom Control Basic programs are installed and

set to autorun, whenever the firmware is updated,

ALL (factory and custom) programs are halted. If

custom Control Basic programs are installed but

NOT set to autorun, whenever the firmware is up-

dated, factory programs are restarted but any (manu-

al) running custom programs are halted at restart.
Change the state of each custom program by using

the Update Manager or loading/running each pro-

gram from the CB Programs menu (or BACstage or

TotalControl).

UPDATE MANAGER

PROGRAM CONFIG ERROR

ENABLE FACTORY:

ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE

NO

In the About menu, ASV will show CUSTOM if any

built-in Control Basic program (1–5) is not running

or has auto-run disabled. See

About the FlexStat on

page 6

.

NOTE: Customized programs are the responsibility

of the user. KMC Controls does not provide

support for such programs.