Advanced) trend logs – KMC Controls FlexStat Operation Guide User Manual

Page 20

Advertising
background image

FlexStat 20

Operation Guide, Rev. R

(Advanced) Trend Logs

TREND LOGS

TREND 1:

TREND 2: TRUE
TREND 3: FALSE
TREND 4: FALSE
TREND 5: FALSE
TREND 6: FALSE
TREND 7: FALSE

TRUE

TREND #1

SPACE TEMPERATURE LOG
OBJECT REF: AI1
LOG ENABLE: TRUE
INTERVAL (MINS): 10
STOP W/FULL: FALSE
RESET COUNT: NO
COUNT: 256
TOTAL CNT: 613

VIEW LOG BUFFER

TL #1–SPACE TEMP

APR17 1:27PM, 71.4

APR17 2:27PM, 71.5
APR17 3:27PM, 71.6
APR17 4:27PM, 71.8
APR17 5:27PM, 76.3
APR17 6:27PM, 81.2
APR17 7:27PM, 82.3

The FlexStat generates one or more default trend

logs that are dependent on options and applications:

Space temperature is always the default trend

log #1. (Before firmware R2.0.0.12, this monitored

AI1, but later firmware monitors AV40 to allow

for a remote space temperature sensor and aver-

age/highest/lowest reading options.)

• If AI2 is configured for discharge air tempera-

ture, this will become default trend log #2. See

Sensor Setup on page 9

.

• Models with

CO

2

sensors will have default trend

log #3. (The onboard CO

2

sensor is AI10, the

optional remote CO

2

sensor is AI9, but the trend

log monitors AV78, which gives the highest of the

two readings.) See also

Damper Setup on page

7

,

(Advanced) CO2 Sensor (and DCV) on page 11

,

Setpoints on page 25

, and

DCV (Demand Control

Ventilation) on page 24

.

Other options that can be user-configured for trend

logs include the following:
• The humidity sensor is AI5 but is mapped to

AV22 for display purposes.

• When AI4 is configured for OAT, OAT is mapped

to AV23 for display purposes.

• The motion sensor is BI6. However, BI6 is ac-

tive only when motion is detected by the sensor.

People sitting quietly in an office, for example,

will not activate the sensor. Unless trend logs

are configured for impractically short intervals,

some or even most motion detections will not be

recorded. Motion sensor occupancy override is

BV24 and standby is BV35—either of these may

be more practical to use as a trend log.

See the

FlexStat Application Guide

and relevant

FlexStat Installation Guide for other desired input

and output objects in an application.
To set the desired object to track, press:
1. Up/Down to move among entries.
2. Enter

to select.

NOTE: The BACnet standard for log intervals

is hundredths of seconds. The simplified

display on the FlexStat converts the value

to minutes. However, BACstage

and

TotalControl

®

do display hundredths of

seconds but in different ways. For a “10”

(minute) interval on a FlexStat display,

TotalControl would show “00:10:00.00”

(hours:minutes:seconds.hundredths of

seconds) and BACstage would show

“60000” (hundredths of seconds) instead.

The trend log buffer may be viewed by scrolling

down and selecting View Log Buffer. The buffer may

also be viewed from the Main Menu by scrolling

down to the

Trend Viewer

(see

page 26

).