Flexstat malfunctions after upgrade, Flexstat – KMC Controls FlexStat Operation Guide User Manual

Page 38

Advertising
background image

FlexStat 38

Operation Guide, Rev. R

• If the USB port does not appear in the drop-

down list, close the tool, remove power to the

FlexStat, disconnect the FlexStat from the USB

port, reconnect the FlexStat to the USB port,

restore power to the FlexStat, and restart the tool.

• For any communication error (such as an “Op-

eration has failed!” message) check all connec-

tions and restart the Firmware Upgrade Tool.

If the HTO-1103 kit was received prior to Feb.

7, 2012 and has Rev. D on the silver label of the

programming pod, see the FlexStat Programming

Pod Jumper Position Service Bulletin SB0212A to

check for the correct jumper position within the

pod.

• For display/interface issues in the Firmware

Upgrade Tool, right-click in the firmware panel

(on the right) and select Restore Defaults.

• To view and download firmware updates from

within the tool or from KMC’s Partner Portal web

site (

partners.kmccontrols.com

), you must log-in

with a valid user name and password.

• Ensure firmware for the correct model is se-

lected in the Firmware Upgrade Tool. If firmware

for the wrong model is accidentally installed, the

outputs will not match the applications/configu-

ration on the display.

NOTE: Backing up the existing settings and

firmware image before or during the

upgrade process (using the Firmware

Upgrade Tool, TotalControl, or BACstage)

is recommended practice.

FlexStat Malfunctions After Upgrade

• After the update process is over, if the FlexStat

display remains blank but the backlight is on or

the display locks up at a later time, check that

the WD jumper is reinstalled on the CORRECT

pins. (See the illustration on the previous page.)

• Check the application configuration.
NOTE: Restoring to the factory defaults and

reconfiguring might be needed if how the

FlexStat operates changes. Read all notes

accompanying the firmware update!

NOTE: If custom Control Basic programs are

installed and set to autorun, whenever the

firmware is updated, ALL (factory and

custom) programs are halted. If custom

Control Basic programs are installed

but NOT set to autorun, whenever the

firmware is updated, factory programs

are restarted but any (manual) running

custom programs are halted at restart.

• Change the state of each custom program by

using the Update Manager or loading/running

each program from the CB Programs menu (or

BACstage or TotalControl).

UPDATE MANAGER

PROGRAM CONFIG ERROR

ENABLE FACTORY:

ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE

NO

NOTE: See also

Control Basic Programs Do Not

Work on page 33

.)

NOTE: Customized programs are the responsibility

of the user. KMC Controls does not provide

support for such programs.