Operation Guide, Rev. R

A cold start does the following in the FlexStat:
• (After zeroing out objects during the restart

process) returns all object values to their relin-

quished defaults (until they are updated by the

FlexStat’s programs).

• Restarts the controller’s Control Basic programs.
• Leaves configuration and programming intact.
NOTE: Menu changes may take up to about two

minutes to write to nonvolatile Flash

memory. If power to the FlexStat is lost

during this time, changes may be lost.

Restarting the FlexStat from its menu,

TotalControl, or BACstage are the

recommended methods.

NOTE: When

power is restored after an outage,

the FlexStat will attempt to do a warm

start as long as the values in RAM are

retained (up to about four hours). If

the the RAM checksum test fails, a cold

start will be done instead. (In custom

Control Basic programming, using the

POWERLOSS command may be desirable

to determine start-up conditions and to take

appropriate actions—see the Help system

in TotalControl or BACstage for more

information.)

ADVANCED
CO2 SENSOR
DATE/TIME
DEVICE
INPUTS
LIMITS
LOOPS

RESTART/RESTORE

RESTART/RESTORE
RESTART:
RESTORE FACTORY: NO

WARM START

To perform a WARM start, do one of the following:
• From the FlexStat menu, select Advanced > Re-

start/Restore > Warm Start.

• From TotalControl or BACstage, select Reinitial-

ize Device > Warm Start.

• Momentarily remove power to the FlexStat.
To perform a COLD start, do one of the following:
• From the FlexStat menu, select Advanced > Re-

start/Restore > Cold Start.

• From TotalControl or BACstage, select Reinitial-

ize Device > Cold Start.

Restore Factory

Restore Factory (restoring the FlexStat to the factory

settings) does the following:
• Clears present values.
• Restores the object database/configuration to the

defaults.

• Restarts the controller’s (factory installed) Con-

trol Basic programs.

NOTE: The

MAC address and device instance are

not restored to their original defaults, and

custom Control Basic programs are not

deleted. If custom Control Basic programs are

installed, all factory programs are restarted

but all custom Control Basic programs are

halted. Custom programs may be restarted by

loading/running the programs from the CB

Programs menu. See

(Advanced) CB (Control

Basic) Programs on page 10

.

CAUTION

When returned to factory defaults, analog out-
puts will go to zero and relays will go to their
normally open state. Before restarting the ther-
mostat, manually override equipment as needed.

CAUTION

After a return to factory defaults, applications are
unconfigured. You must select the desired appli-
cation and appropriate settings before connected
equipment will operate properly. (See

(Advanced)

Application and Additional Setup on page 7

.)

To restore the FlexStat to factory settings:
1. Select Restore Factory from the Advanced > Re-

start/Restore menu.

2. When prompted for the required restart, press

Enter. (To Cancel, press the right button and then

Enter or just let the display time-out).

3. After the FlexStat has restarted, review the set-

tings and reconfigure as needed.

ADVANCED
CO2 SENSOR
DATE/TIME
DEVICE
INPUTS
LIMITS
LOOPS

RESTART/RESTORE

RESTART/RESTORE
RESTART: NO
RESTORE FACTORY:

YES

RESTART REQUIRED!

CANCEL

RESTART