KMC Controls FlexStat Operation Guide User Manual

Page 13

Advertising
background image

FlexStat 13

Operation Guide, Rev. R

position, not the minimum outside air

percentage.) The OA damper shall be at this

position when Space CO2 is at

or below

CO2 BASE

. The value is determined using

DCV DAMPER SETUP.

OA FULL = The outside air damper position (5%

default) for the OA AREA plus the people

occupying the space. The outside air

damper shall be at this position when

Space CO2 is at CO2 MAX. The value is

determined using DCV DAMPER SETUP.

OA HIGH VENT = The highest temperature (80°

F default) that would use 100% OA for

recovery.

OA LOW VENT = The lowest temperature (65° F

default) which would use 100% OA for

recovery. (If outside air temp is between OA

low vent and OA high vent, the outside air

damper will be open 100% during recovery

mode.)

OA MAX = The maximum allowable % of outside

air damper position (40% default) for

ventilation (not cooling) purposes. The value

is determined using DCV DAMPER SETUP.

OA PURGE = During the 60 minutes prior to

scheduled start time, the outside air

damper will open to this position (0%

default) to perform a purge of the zone. The

value is determined using DCV DAMPER

SETUP.

Night Flush

(Economizer

Cooling)

Startup*

Normal

Occupancy

Standby*

Cooling

Setpoint

Scheduled

On Time

OAD

Position

Scheduled

Off Time

(Unoccupied)

(Occupied)

Occupancy

Override*

(*Available only on FlexStats with motion sensors)

Standby

Recovery

(Manual)

Override

Pre-purge

(Unoccupied)

VENT MODE = Displays (only) in which ventilation

mode the FlexStat is functioning (see

illustration):
Normal—Typical ventilation during

the occupied period (after Pre-purge,

Startup, or Recovery modes have

of them. (If there is a Low Limit alarm,

however, these signals are overridden, and

the damper is closed.)

The three types of configurations have various com-

binations of the following DCV OPTIONS.
CLG DESIGN TEMP
= The highest outside air

temperature (95° F default) for which the

building’s cooling system is designed.

CO2 MAX (PPM) = The desired maximum CO

2

concentration level during an occupied

period (1000 ppm default). In BASIC and

STANDARD DCV modes, the economizer

damper will modulate to fully open at this

level.

CO2 SETPT (PPM) = The desired CO

2

level at which

point the economizer damper will begin

modulating open from MIN POSITION

(600 ppm default). Below this level,

the economizer damper will be at MIN

POSITION during Occupied mode. (This

can be adjusted no lower than the CO2

BASE.)

CO2 BASE (PPM) = The presumed average CO

2

concentration level of outside air at the

building’s location (400 ppm default).

DCV DAMPER SETUP = A test mode is used to

determine proper outside air damper

position values for OA AREA, OA FULL,

OA MAX, and OA PURGE. The required

airflows for these four positions are

determined by ASHRAE 62.1-2007 section

6.2.6.2. A technician/balancer uses this

menu to set specific damper positions and

measure the resulting airflows. The damper

positions are then correlated to the required

airflows. One hour after the setup mode is

activated, it will return to the default AUTO

setting, or it can be manually set to AUTO

after testing is completed.

FAN MAX OFF (MINS) = The maximum time (30

default) the supply fan may remain off

during occupied times.

HTG DESIGN TEMP = The lowest outside air

temperature (20° F default) for which the

building’s heating system is designed.

OA AREA = The outside air damper position (2%

default) required to provide the outdoor

air rate based on the zone area. This is

based on ASHRAE 62.1-2007 section 6.2.6.2.

(Note that this value represents the damper