Joining communication cable, Changing jumper positions – Vintage Cellars Through-the-Wall Wine Cellar Cooling System Manual User Manual
Page 31
 
31
Joining Communication Cable
 
 
 
Changing Jumper Positions
(Averaging readings from Remote Sensor)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
If using multiple Remote Temperature/Humidity 
sensors in your application, refer to the photos 
showing the need to change the jumper locations 
internal to the control board on each remote 
sensor (up to 3 maximum). 
 
For the control to average all of the sensors 
utilized (if more than one), the jumper must be in 
different positions on the pins. 
 
There are three pin settings. To access the jumper: 
1. Remove the two-set screws holding on the 
 plastic cover. This procedure allows the control 
 to go to each remote sensor in sequence to 
 average. Failure to perform this procedure will 
 result in the system reading only one sensor 
 and not the average of multiple sensors. 
 
NOTE: If multiple sensors control the WG 
unit, change factory default in configuration 
setting 10 to “averaging.” Obtain access code 
from Air Innovations service department to 
use in configuration 8 to reach configuration 
10. 
Jumper position 1
Jumper position 2
Jumper position 3
 
 
 
 
 
 
 
Important
Wine Guardian cooling systems are supplied with 50 feet of 6 wire, Cat 3 twisted pair 
communication cable with RJ11 type connectors. Caution must be taken when connecting 
two lengths of communication cable (splicing) to ensure uniform wire color before and after 
splice. An RJ11 Modular 6 wire STRAIGHT THROUGH type coupler is the ONLY coupler 
approved for splicing Wine Guardian twisted pair communication cable.