Vintage Cellars Through-the-Wall Wine Cellar Cooling System Manual User Manual
Page 33
 
33
Deg F or Deg C
 
 
 
 
 
Setting 1
Press the “Down” arrow to change temperature 
from Deg F to Deg C. 
Press the “Up” arrow to change temperature 
from Deg C to Deg F. 
Low temperature 
alarm set point 
 
 
 
 
 
Setting 2
Press “Mode” button to advance to Setting 2.
Press the “Up” or “Down” arrow buttons to 
adjust to the desired set point. Factory default 
is 50 Deg. F. 
Setting 3
Press “Mode” button to advance to Setting 3.
Press the “Up” or “Down” arrow buttons to 
adjust to the desired set point. Factory default 
is 65 Deg F. 
 
 
 
Low humidity 
alarm set point 
 
 
 
 
Setting 4
Press “Mode” button to advance to Setting 4.
Press the “Up” or “Down” arrow buttons to 
adjust to the desired set point. Factory default 
is 5%. 
 
 
 
High humidity 
alarm set point 
 
 
 
 
Setting 5
Press “Mode” button to advance to Setting 5.
Press the “Up” or “Down” arrow buttons to 
adjust to the desired set point. Factory default 
is 95%. 
 
 
 
Add or remove 
humidifier 
 
 
 
 
 
 
 
Setting 6
Press “Mode” button to advance to Setting 6.
Press the “Up” or “Down” arrow buttons to 
adjust to the desired set point. Factory default 
is zero (0). 
Zero (0) = No humidifier 
One (1) = Stand-alone remote mounted 
humidifier 
Two (2) = Integral Wine Guardian mounted 
humidifier (Not for TTW applications) 
Fan AUTO or ON 
 
 
 
 
Setting 7
Press “Mode” button to advance to Setting 7.
Press the “Up” or “Down” arrow buttons to 
adjust number to the desired set point. Factory 
default is zero (0). 
Zero (0) = Auto – fan only turns on when 
there is a call for cooling or heating 
One (1) = Fan On – fan remains on 
continuously