Advanced Settings- 
Special access 
required. Contact 
Wine Guardian 
Service Department 
for access code 
 
Setting 8
Press “Mode” button to advance to Setting 8.
Press the “Up” or “Down” arrow buttons to 
adjust number to the access code. Press 
“Mode” button to continue onto setting 9 
through 19. 
Compressor anti-
short cycling time 
Setting 9
Press “Mode” button to advance to Setting 9.
Press the “Up” or “Down” arrow buttons to 
adjust to the desired time in one minute 
increments. Maximum is 10 minutes, minimum 
is 0 minutes. 
Compressor anti-short cycling time is the amount 
of allowable time between compressor stop and 
restart. Rapid start/stop of compressors can cause 
premature failure. Factory default is 5 minutes. 
WINE GUARDIAN DOES NOT 
RECOMMEND SETTINGS LOWER THAN 
FACTORY DEFAULT. 
Set up remote 
sensor 
 or thermostat 
Setting 10
Press “Mode” button to advance to Setting 10.
Press the “Up” or “Down” arrow buttons to 
adjust to the desired setting. 
Remote sensor 
Remote interface 
Local interface – Through-the-wall unit only 
Averaging – Jumper position within sensors 
must be adjusted. See page 27. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Room sensor 
calibration 
Setting 15
Press “Mode” button to advance to Setting 15.
Press the “Up” or “Down” buttons to adjust to 
the desired setpoint. Maximum setting is +5, 
minimum setting is -5. Factory default is zero 
(0). Sensor calibration setpoint changes the 
actual display reading (temperature only) by 
the value of this setting. 
Example: Sensor reading = 55 Deg F 
Setting 15 Set to +4 
Display reading = 59 Deg F 
 
 
 
 
 
 
 
 
 