Table 1 – Physical Data--Unit 50VL--A

UNIT SIZE

24

30

36

42

48

60

NOMINAL CAPACITY (ton)

2

2---1/2

3

3---1/2

4

5

SHIPPING WEIGHT* lb.

SHIPPING WEIGHT* (kg)

295

134

307

139

365

166

421

191

439

199

467

212

COMPRESSORS

Quantity

Scroll

1

REFRIGERANT (R---410A)

Quantity lb

Quantity (kg)

6.0

2.7

5.6

2.5

9.5

4.3

8.8

4.0

9.4

4.3

12.5

5.7

REFRIGERANT METERING DEVICE

TXV

OUTDOOR COIL

Rows...Fins/in.

Face Area (sq ft)

1...21

11.9

1...21

13.6

2...21

15.4

2...21

13.6

2...21

17.5

2...21

21.4

OUTDOOR FAN

Nominal Cfm

Diameter in.

Diameter (mm)

Motor Hp (Rpm)

2500

24

609.6

1/10 (810)

2700

24

609.6

1/10 (810)

2800

24

609.6

1/5 (810)

3000

26

660.4

1/5 (810)

3200

26

660.4

1/5 (810)

3600

26

660.4

1/5 (810)

INDOOR COIL

Rows...Fins/in.

Face Area (sq ft)

3...17

3.7

3...17

3.7

3...17

3.7

3...17

4.7

3...17

4.7

3...17

5.7

INDOOR BLOWER

Nominal Cooling Airflow (Cfm)

Size in.

Size (mm.)

Motor HP (RPM)

800

10x10

254x254

1/2 (1050)

1000

10x10

254x254

1/2 (1050)

1200

11x10

279.4x254

3/4 (1000)

1400

11x10

279.4x254

3/4 (1075)

1600

1750

11x10

279.4x254

11x10

279.4x254

1.0 (1075)

1.0 (1040)

HIGH---PRESSURE SWITCH

(psig) Cut---out Reset (Auto)

650 +/--- 15

420 +/--- 25

LOSS---OF---CHARGE / LOW---PRES-

SURE SWITCH (Liquid Line) (psig)

cut---out Reset (auto)

20 +/--- 5

45 +/--- 10

RETURN---AIR FILTERS†}

Throwaway Size in.

Throwaway Size (mm)

20x20x1

508x508x25

20x24x1

508x610x25

24x30x1

610x762x25

24x36x1

610x914x25

*For 460 volt units add 14 lb (6.35 kg) to the shipping weight.
{

Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating air-

flow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08

in. W.C.
}

If using accessory filter rack refer to the filter rack installation instructions

for correct filter sizes and quantity.

Table 2 – Minimum Airflow for Safe Electric Heater Operation (CFM)

SIZE

24

30

36

42

48

60

Cfm

800

1000

1200

1400

1600

1750